• Function
Process control including keeping airflow, pressure, and the amount of flow constant, can be
exercised using feedback signals (4 to 20mA, 0 to 10V) from a detector.
Or, it is also possible to always set 0 for integral and differential at terminal input.
⇒Refer to "PID control instruction manual: E6581879" for details.
[Parameter setting]
Title
Function
fpid Process input value of PID control
PID control waiting time
f359
PID control
f360
f361 Delay filter
Proportional gain
f362
Integral gain
f363
Differential gain
f366
f367 Process upper limit
f368 Process lower limit
f369 PID control feedback signal selection
Process increasing rate (speed type
f372
PID control)
Process decreasing rate (speed type
f373
PID control)
PID forward/reverse characteristics
f380
selection
f389
PID control reference signal selection
*1: Default setting value vary depending on the setup menu setting. Refer to section 11.5.
Adjustment range
f368 - (Hz)
0-2400 (s)
0: Disabled
1: Process type PID control
2: Speed type PID control
0.0-25.0 (s)
0.01-100.0
0.01-100.0
0.00-2.55
0.0-fh (Hz)
0.0- (Hz)
0: Disabled
1: Terminal VIA
2: Terminal VIB
3: Terminal VIC
4 to 6: -
0.1-600.0 (s)
0.1-600.0 (s)
0: Forward
1: Reverse
0: fmod/f207 selected
1: Terminal VIA
2: Terminal VIB
3: fpid
4: RS485 communication
5: UP/DOWN from external logic
input
6: CANopen communication
7: Communication option
8: Terminal VIC
9, 10: -
11: Pulse train input
F-79
E6581611
Default setting
0.0
0
0
0.1
0.30
0.20
0.00
60.0 *1
6
0.0
0
10.0
10.0
0
0