6.30 Forced fire-speed control function

f650 : Forced fire-speed control selection
f294 : Preset-speed frequency 15
• Function
With forced fire-speed control, operate the motor at the specified frequency in case of an emergency.
Two kinds of operation are selectable by assignment of input terminal function.
(1) Input terminal function 56 (FORCE) : Input signal is retained once signal is ON.
Note: This case needs to power off in order to stop
(2) Input terminal function 58 (FIRE)
Note: In either case, power terminal should be off in order to stop.
[Parameter setting]
Title
Forced fire-speed control selection
f650
Preset-speed frequency 15
f294
[Setup example of input terminal]
When the terminal "RES" is assigned.
Title
Input terminal selection 3A (RES)
f113
Each setting value 57, 59 are reverse signal.
"fire" and output frequency are blinking during forced run operation and fire-speed operation.
Motor runs at the speed set by the parameter "f294".
Motor is forced to operate in case of light failure.
: Input signal is retained once signal is ON.
Motor runs at the speed set by the parameter "f294".
Function
0: Disabled
1: Enabled
ll-ul (Hz)
Function
Adjustment range
0 - 203
F-115
Adjustment range
Default setting
Setting value
56 ( Forced run operation )
or
58 ( Fire speed operation )
E6581611