f856
f870
f871 Block write data 2
f875 Block read data 1
f876 Block read data 2
6
f877 Block read data 3
f878 Block read data 4
f879 Block read data 5
f899 Communication function reset
*1: Disabled............ Indicates that the inverter will not be tripped even if a communication error occurs.
Trip................... The inverter trips when a communication time-over occurs.
Alarm ............... When a communication time-over occurs, an alarm can be output from the output terminal.
*2: Default setting values vary depending on the setup menu setting. Refer to section 11.5.
Note2) Changes to the parameters f800, f801 and f806 do not take effect until the power is turned
Title
Function
Number of motor poles for
communication
Block write data 1
In this case a trip information err5 flashes on and off on the operation panel.
Output terminal function: 78 (RS485 communication error) or 79 (RS485 communication
error reverse)
off and then on again.
Adjustment range
1: 2 poles
2: 4 poles
3: 6 poles
4: 8 poles
5: 10 poles
6: 12 poles
7: 14 poles
8: 16 poles
0: No selection
1: Communication command 1
2: Communication command 2
3: Frequency command value
4: Output data on the terminal
block
5: FM analog output
6: Motor speed command
0: No selection
1: Status information 1
2: Output frequency
3: Output current
4: Output voltage
5: Alarm information
6: PID feedback value
7: Input terminal monitor
8: Output terminal monitor
9: Terminal VIA monitor
10: Terminal VIB monitor
11: Terminal VIC monitor
12: Input voltage (DC detection)
13: Motor speed
14: Torque
0: -
1: Reset (after execution: 0)
F-138
E6581611
Default setting
2
0
0
0
0
0
0
0
0