Psc-A32Mn - Hitachi PC-ARF Technical Catalogue

Table of Contents

Advertisement

3 Features and benefits
Centralised remote controls

3.2.2 PSC-A32MN

The central station mini (PSC-A32MN) is connected to H-LINK system and used for the central control and monitoring of
the air conditioners.
Touch Screen Central Station with attractive design and reduced dimensions.
Monitoring of Operating Conditions for Block/Groups.
Flexible selection of the Blocks/Groups. Up to 32 groups can be created and controlled by one PSC-A32MN. It allows
the following combinations (4 blocks x 8 groups, 8 blocks x 4 groups, 2 blocks x 16 groups, 16 blocks x 2 groups).
A maximum number of 16 indoor units by group is allowed, with a maximum of 160 indoor units per H-LINK II system.
Up to 8 central stations mini (PSC-A32MN) can be connected to a H-LINK.
The main control functions are: Run/Stop Operation Mode Change, Fan Speed Control, Swing Louver Direction Con-
trol, Temperature Setting, Permitting/Prohibiting Operation by Remote Control Switch.
Optional Functions:
-
New function "Setting temperature range of the remote control" for limiting the minimum temperature value in cool-
ing operation, or the maximum temperature value in heating operation.
-
Schedule Operation (Run/Stop and Temperature Setting) for Block/Group
-
Run/Stop, Emergency Stop and Demand Function by External Input
-
Run an Alarm Output by External Output
-
Control Exception Function of All Run/Stop Command for Selected Groups
-
Control Exception Function of All Run/Stop Command for Selected Groups by External Input
-
Indication and Calculation of Unit Accumulated Operation Time of Each Group
Indication of Alarm History Record
-
-
Registering Name of Blocks and Groups
-
Registration and Indication of Service Contact Information
Operation modes can be selected as Normal Operation or Run/Stop Only.
Brief explanation of the different icons by pressing the "Icon Guide" button.
A system configuration example is shown below:
Max 8 units in the same H-LINK are available.
(Set RSW1 correctly)
Central station
(PSC-A32MN)
Wiring for remote control switch
Controlled by central station
(Remote control group)
41
41
TCGB0106 rev.0 - 12/2014
PSC-A32MN Touch Screen Central Station mini
Max. 64 remote control group and max 160 indoor units are available.
Group
Without
transmission
wiring
(For H-LINK II only)
Group
Without
remote
With
control
transmission
switch
wiring
3
H-LINK
transmission
wiring
Group
Group
Without
remote
control
switch

Advertisement

Table of Contents
loading

Table of Contents