7 Gateways for building management systems
HC-A16KNX

Error code list:
Code (in Hexadecimal)
0
No Error
1~98
See Hitachi documentation
99
Unit not configured

7.2.4.3 Configuration method

Every HC-A16KNX can control up to 16 indoor units, considering that in the same H-LINK can be connected up to 160
indoor units, it must be set which indoor units are selected for each HC-A16KNX.
Setting concept consist in an "Id" table listing up to 16 numbers for the assignation of each OU+IU addresses as shows
the following example.
N O T E :
KNX software (ETS) is using indoor units from 1 to 16, corresponding to the ID from 0 to 15, so BMS is using indoor unit Id+1. For
example, in case you have 6 indoor units, declared as unit 1 to 6 on ETS, Ids have to be set from 0 (unit 1) to 5 (unit 6).
It can be selected for 1 HC-A16KNX up to 16 indoor units from 16 different refrigerant cycles or 16 indoor units from the same refriger-
ant cycle.
C A U T I O N :
Be sure not to set same Indoor Unit to more than one HC-A16KNX. This error is undetectable and can cause undesired operations.
643
643
TCGB0106 rev.0 - 12/2014
Description
Refrigerant cycle
Id
address
00
00
01
00
02
00
03
00
04
00
05
00
06
00
07
00
08
00
09
00
10
00
11
00
12
00
13
00
14
12
15
25
Indoor unit address
00
01
02
03
04
05
06
07
08
09
10
11
12
13
02
61
7