Electrical Wiring - Hitachi PC-ARF Technical Catalogue

Table of Contents

Advertisement

7 Gateways for building management systems
HC-A(8/64)MB
Units Id Configuration
Automatic address can be done by pushing
Manual address configuration can be done by the assignation of each Id to a specific H-LINK address
Outdoor unit address (Ou) and Indoor unit address (Iu)
-
Confirm the configuration by pressing
Refresh button shall be pressed when modify the units connected to the net

7.1.3 Electrical wiring

Name
Connection
X1
Power supply (1)
X3
Ethernet (1)
X4
H-LINK (1)
X5
RS485 (1)
X6
USB (1)
N O T E
(1): These cables must be field supplied.

DIP switch setting
Factory
Name
Function
SW1
Configuration
632
632
TCGB0106 rev.0 - 12/2014
Use 0.75 mm
wires which are not lighter than the polychloroprene sheathed flexible cord (code
2
designation 60245 IEC 57)
Category 5 or higher LAN cables
PC connection: Use a crossed cable (1 cable set available in Net configuration Kit, model code
7E513206) for direct connection.
LAN connection: Use a direct cable (field-supplied) for connection to a commercial distributor (Hub).
Twisted pair shielded cable 0.75 mm².
Shield must be grounded in one side only.
3 cores cable harness 0.75 mm² grounded in one side only. Use different colour for each cable.
USB Mini-B plug cable (1 cable set available in Net configuration Kit, model code 7E513206)
Description
setting
SW1-1: Modbus end resistance.
SW1-2: Not used (keep always "ON")
Cable specification