H-Link - Hitachi PC-ARF Technical Catalogue

Table of Contents

Advertisement

6 Building air conditioning controls
CSNET Manager LT/XT

6.2.2.5 H-LINK

HC-A64NET is compatible with the H-LINK 2 and the old version called H-LINK (H-LINK 1) units.
Connection of both H-LINK 1 and H-LINK 2 units in the same H-LINK unit is possible considering the unit limitations and
addressing.
H-LINK 2 number of connectable devices is up to a maximum of 200 devices in the H-LINK 2 line. A CSNET WEB, an
Indoor Unit, an Outdoor Unit, a HC-A64NET or other devices with H-LINK address are considered as a device.
N O T E
CSNET Manager is not considered as an H-LINK device.
PC-A1IO, KPI or DX-Kit count as a normal indoor unit.
When there is a central control device like CSNET Manager, the maximum number of total units (indoor and outdoor units)
for only 1000 meters of H-LINK line is shown on the following table:
H-LINK line length could be up to 1000 meters, they could be increased to 5000 meters using up to 4 PSC-5HR. Each of
them adds 1000 meters to the line, affecting the quantity of indoor unit that can be connected to the same H-LINK.
Each H-LINK line repeater (PSC-5HR) counts as 16 indoor units. The following table summarize the affection of the PSC-
5HR to the indoor and outdoor unit maximum number.
Number of PSC-5HR
0
1
2
3
4
Therefore, considering the previous maximums and the number of PSC-5HR, the maximum number of indoor units with
one central control, on that case CSNET WEB, is shown on the following table and graphic.
160
140
120
100
80
60
40
20
0
Outdoor units
0 PSC-5HR
64
1 PSC-5HR
64
2 PSC-5HR
64
3 PSC-5HR
64
4 PSC-5HR
64
The maximum number of Indoor units connectable to a HC-A64NET is 64, and for the outdoor units are 64.
Note that CSNET Manager connected to a PSC-A160WEB1 can control up to 160 units. Connecting 8 PSC-A160WEB1 to
one CSNET Manager we can get the maximum number of connectable units of 1280.
519
519
TCGB0106 rev.0 - 12/2014
Outdoor units
Indoor units
Units (outdoor and indoor)
H-LINK devices
Maximum length of H-LINK
1000 meters
2000 meters
3000 meters
4000 meters
5000 meters
Maximum Indoor Unit Quantity
Maximum indoor units quantity
1
4
8
12
16
20
24
28
160
160
160
160
156
152
148
156
152
148
144
140
136
132
140
136
132
128
124
120
116
124
120
116
112
108
104
100
108
104
100
96
92
88
84
Maximum number
64
160
176
200
Maximum number of indoor and outdoor units
32
36
40
44
48
52
56
60
144
140
136
132
128
124
120
116
128
124
120
116
112
108
104
100
112
108
104
100
96
92
88
84
96
92
88
84
80
76
72
68
80
76
72
68
64
60
56
52
176
160
144
128
112
0 PSC-5HR
1 PSC-5HR
2 PSC-5HR
3 PSC-5HR
4 PSC-5HR
64
112
96
80
64
48
6

Advertisement

Table of Contents
loading

Table of Contents