Mitsubishi Electric GOT2000 Series Connection Manual page 178

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

(20) RS485 connection diagram 20)
GOT side
SDA
SDB
RDA
RDB
SG
RSA
CSA
RSB
CSB
*1
*2
*3
*4
(21) RS485 connection diagram 21)
GOT side
SDA
SDB
RDA
RDB
SG
RSA
RSB
CSA
CSB
*1
*2
*3
*4
3 - 52
3.3 Connection Diagram
Terminating resistor(150Ω 1/2W)
* 4
1
6
2
7
* 3
5
3
4
8
9
Pin No. of control equipment differs depending on the model. Refer to the following table
Signal name
DA
DB
SG
For GT27 and GT25 (except for GT2505-V), terminating resistor should be provided for an Interface converter and a control
equipment which will be terminals.
Connect FG grounding to the single-sided end of a cable shield line.
Set the terminating resistor of GOT as follows.
For GT27 and GT25 (except for GT2505-V), set the terminating resistor to "Disable".
For GT2505-V and GT21, set the terminating resistor to "110 Ω".
➠ ■3.
Connecting terminating resistors
*2
* 3
* 4
* 4
* 4
* 4
Pin No. of control equipment differs depending on the model. Refer to the following table.
Signal name
DA
DB
SG
Set the terminating resistor setting switch of the GOT main unit to "110Ω".
➠ ■3.
Connecting terminating resistors
Connect FG grounding to the single-sided end of a cable shield line.
The signals RSA, RSB, CSA, and CSB are not provided for
* 2
Control equipment side
* 1
DA
DB
SG
* 3
Model of control equipment
CMS
SDC45/46
CMF015
Pin No.
Pin No.
C10
5
C11
6
C12
10
Control equipment side
* 1
DA
DB
SG
* 3
Model of control equipment
DMC10
SDC15
Pin No.
Pin No.
4
16
5
17
6
18
. Return connection is not required.
Control
equipment
side
* 1
DA
DB
SG
MQV
MVF
MPC
Pin No.
Pin No.
7
1
8
2
9
7
Control equipment side
* 1
DA
DB
SG
SDC25/26
AUR350C
SDC35/36
AUR450C
Pin No.
Pin No.
22
DA
23
DB
24
SG
RX
Pin No.
1
2
3