10.5 Indicating Controller Side Setting
Indicating controller
Communication converter
10.5.1
Connecting to ACS-13A, DCL- 33A, JC, JCM-33A, JIR-301- M, PCD-300
Series, PC-900 Series (PC-955-[ ]/M,C5, PC- 935-[ ]/M,C5)
■1. Communication settings
Make the communication settings by operating the key of the indicating controller.
*1
Transmission speed
Data bit
Parity bit
Stop bit
*2*3
Station No.
Communication protocol
*1
Adjust the settings with GOT settings.
*2
Avoid duplication of the station No. with any of the other units.
*3
When setting the "95" to the station No., the read-out of data cannot be performed.
10.5.2
Connecting to FCD-100, FCR- 100, FCR-23A, FIR Series, PC-900 Series
(PC-955-[ ]/ M,C, PC-935-[ ]/M,C)
■1. Communication settings
Make the communication settings by operating the key of the indicating controller.
*1
Transmission speed
Data bit
Parity bit
Stop bit
*1*2
Station No.
Communication protocol
*1
Adjust the settings with GOT settings.
*2
When setting the "95" to the station No., the read-out of data cannot be performed.
POINT
POINT
POINT
(1) Shinko Technos indicating controller
For details of Shinko Technos indicating controller, refer to the following manual.
➠
User's Manual of the Shinko Technos indicating controller
(2) Communication converter
For details on communication settings of the communication converter, refer to the following
manual.
➠
User's Manual of communication converter
Model name
ACS-13A, DCL-33A, JC,
JCM-33A, JIR-301-M, PCD-300 Series, PC-900 Series (PC-955- /M,C5, PC-935- /
M,C5)
FCD-100, FCR-100, FCR-23A,
FIR Series, PC-900 Series (PC-955- /M,C, PC-935- /M,C)
IF-400
Item
9600bps, 19200bps
7bits (fixed)
Even (fixed)
1bit (fixed)
0 to 95
Shinko protocol
Item
9600bps, 19200bps
7bits (fixed)
Even (fixed)
1bit (Fixed)
0 to 95
Shinko protocol
Set value
Set value
10.5 Indicating Controller Side Setting
Refer to
➠
10.5.1
➠
10.5.2
➠
10.5.3
10
10 - 17