Mitsubishi Electric GOT2000 Series Connection Manual page 243

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

(2) Setting transmission speed (SW3)
Set the same transmission speed of the GOT.
*1
Setting
4
5
6
*1
Only transmission speeds available on the GOT side are shown.
(3) Setting command level/parity/transmission code (SW4)
Settings
2
(fixed)
(4) Setting the 1:1/1:N procedure switch
(5) Setting the terminating resistor connection switch
SW3
Command level
Levels 1, 2 and 3 enabled
OFF (1:N procedure)
ON (terminating resistor attached)
Settings
4800bps
9600bps
19200bps
SW4
Setting details
Parity
Even
Settings
Settings
4.2 Serial Connection
Transmission code
ASCII 7 bits
2 stop bits
4 - 41
4

Advertisement

Table of Contents
loading