3.5.6
Connecting to DMC50
■1. Communication settings
Make the communication settings by operating the Smart Loader Package (SLP-D50/SLP-H21)of the temperature
controller.
*1
Transmission speed
Communication mode
Data bit
Parity bit
Stop bit
*2*3*4
Module address
*1
*2
*3
*4
■2. Module address setting
Set the module address using the rotary switch for module address.
3.5.7
Connecting to SDC45/46
■1. Communication settings
Make the communication settings by operating the Smart Loader Package (SLP-C45) of the temperature controller.
*1
Transmission speed
*2
Communication mode
Data bit
*1
Parity bit
Stop bit
Communication minimum response time
*3*4
Station address
*1
*2
*3
*4
*5
3 - 64
3.5 Control Equipment Side Setting
Item
Adjust the settings with GOT settings.
Set the module address using the rotary switch for module address.
Do not set to "0".
Select the module address without overlapping with that of other units.
Rotary switch for the module address
Item
*5
Adjust the settings with GOT settings.
Set to CPL.
Do not set to "0".
Select the station address without overlapping with that of other units.
When using the interface converter CMC10L, set the communication minimum response time to 3ms or more.
9600bps, 19200bps, 38400bps
CPL
8bits (fixed)
Even (fixed)
1bit (fixed)
0 to F
9600bps, 19200bps, 38400bps
CPL
7bits, 8bits
Odd, even, none
1bit, 2bits
1 to 250ms
0 to 120
Set value
Set value