13.3 Connection Diagram

The following diagram shows the connection between the GOT and the PLC.
13.3.1
RS-232 cable
■1. Connection diagram
(1) RS232 connection diagram 1)
(2) RS232 connection diagram 2)
(3) RS232 connection diagram 3)
GOT side
CD
1
RD(RXD)
2
SD(TXD)
3
ER(DTR)
4
SG
5
DR(DSR)
6
RS(RTS)
7
CS(CTS)
8
-
9
GOT side
CD
1
RD(RXD)
2
SD(TXD)
3
ER(DTR)
4
SG
5
DR(DSR)
6
RS(RTS)
7
CS(CTS)
8
-
9
GOT side
(terminal block)
SD
RD
ER
DR
SG
RS
CS
NC
NC
TOSHIBA MACHINE
PLC side
CI
1
TXD
2
RXD
3
DSR
4
SG
5
DTR
6
CTS
7
RTS
8
CD
9
TOSHIBA MACHINE
PLC side
N.C.
1
TXD
3
RXD
2
N.C.
6
SG
5
DTR
4
CTS
8
RTS
7
N.C.
9
TOSHIBA MACHINE
PLC side
RXD
3
TXD
2
DSR
4
DTR
6
SG
5
CTS
7
CI
1
RTS
8
CD
9