ABB i-bus KNX Product Manual page 103

Fan coil actuators fca/s
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
Cycle time of PWM
in s [10...6,000]
Options:
For setting the cycle time for the pulse width modulation.
If the control value is received via a 1 bit value, this parameter serves as the basis for calculation of the
control of the output with
Bus voltage failure/recovery
Forced operation
Fault of the control value (control fault)
Characteristic correction
Opening time of valve drivein s [10...6,000]
Options:
With this parameter, a time is set in seconds that the connected valve requires to move from position 0%
(valve closed) to position 100% (valve fully open).
Note
The time should be taken from the technical data of the valve, and it corresponds with the total runtime.
Closing time of valve drivein s [10...6,000]
Options:
With this parameter, a time is set in seconds that the connected valve requires to move from position
100% (valve open) to position 0% (valve fully closed).
Note
The time should be taken from the technical data of the valve, and it corresponds with the total runtime.
10...180...6,000
10...180...6,000
10...180...6,000
FCA/S 1.x.x.1 | 2CDC508134D0202 101