ABB i-bus
KNX
Commissioning
Reaction after bus voltage recovery
Options:
This parameter determines the reaction of the output at bus voltage recovery. After bus voltage recovery, a
Reference adjustment
controlled.
Unchanged: The last valve control is restored.
Select: A value is determined. Active priorities override the parameterized control.
Valve is
Options:
This parameter determines whether the valve is defined as a heating valve or cooling valve.
Switch on time for valve drive
from 0 to 100 % in s [10...6,000]
Options:
This parameter sets the time that the output switches on to move the valve drive or the valve from 0%
(closed) to position 100% (fully opened).
The time required should be taken from the technical data of the valve.
Unchanged
Select
of the valve drive is always carried out. After this, the current control value is
Dependent parameter:
Control value in % [0...100]
Options:
0...100
This parameter determines the control of the output after bus voltage recovery in %.
Heating valve
Cooling valve
10...180...6,000
FCA/S 1.x.x.1 | 2CDC508134D0202 105