ABB i-bus
KNX
Commissioning
No.
51
This communication object is enabled if the parameter Enable direct operation has been selected with the option Yes in
Parameter window E, F, G: Fan
has been selected with the option Yes in
Via the 1-bit communication object the device can receive a control value for fan speed 1.
Limitations through forced operation or one of the four limitations 1...4 are retained. Automatic operation is disabled.
communication object Automatic ON/OFF reactivates automatic operation.
If several ON telegrams are received consecutively in a short period of time at various Switch speed x (x = 1...3)
communication objects, the value last received is the one that will control the fan. An OFF telegram to one of the three
communication objects Switch speed x (x = 1...3) switches the fan off.
Telegram value:
52
See communication object 51
53
See communication object 51
54
This communication object is enabled if the parameter Enable direct operation has been selected with the option Yes in
Parameter window E, F, G: Fan
1-bit has been selected with the option Yes in
With this communication object, the fan can be switched one fan speed further up or down via a 1 bit telegram. Switching
(up/down) is determined by the telegram value.
With multiple manual up or down switching, the required speed will be increased or reduced by a speed step. This is feasible
until the maximum or minimum possible speed is reached. The parameterized limitations are taken into account here.
Further up or down telegrams are ignored and not executed. Each new switching telegram initiates a recalculation of the
required speed.
Telegram value:
55
This communication object is enabled if the parameter Enable communication object "Status Fan On/Off" 1-bit has been
selected with the option Yes in
The communication object receives the communication object value 1 (ON), if at least one fan speed is not equal to zero
(OFF). The value of the communication object is sent if not equal to zero. This communication object thus defines the status
of the fan, whether it is switched on or off.
Telegram value:
Functionality
Switch speed 1
(Multi-level), p. 124, and the parameter Enable communication object "Switch speed x" 1-bit
0 = Fan OFF
1 = Fan ON in speed 1
Switch speed 2
Switch speed 3
Fan speed up/down
(Multi-level), p. 124, and the parameter Enable communication object "Fan speed up/down"
0 = Switch fan speed DOWN
1 = Switch fan speed up
Status Fan ON/OFF
Parameter window Status messages
0 = OFF
1 = ON
Note
Some fans require an ON telegram before you set a fan speed. Using the communication object Status fan ON/OFF,
the fan can, for example, be switched on centrally with a switch actuator via the main switch.
communication object name
Fan E, F, G
Parameter window Direct operation
Fan E, F, G
Parameter window Direct operation
Fan E, F, G
(Multi-level), p. 129.
Data type
1 bit
DPT 1.001
(Multi-level), p. 143.
1 bit
DPT 1.007
(Multi-level), p. 143.
1 bit
DPT 1.001
FCA/S 1.x.x.1 | 2CDC508134D0202 217
Flags
C, W
C, W
C, T