Commissioning
3.2.3.16

Parameter window Status messages (single speed)

This is the parameter window where status messages are defined.
This parameter window is visible if the option Enabled as fan has been selected under the parameter
Outputs E, F, G in
Enable communication object
"Status byte fan" 1-byte
Options:
From this status byte the states control values A or C, automatic, forced operation and the four limitations
are indicated directly via a 1-bit coding.
For further information see:
Yes: The communication object Status byte fan is enabled.
152 2CDC508134D0202 | FCA/S 1.x.x.1
Parameter window Enable output
No
Yes
Status byte
Dependent parameter:
Send object value
Options:
No, update only
On change
After request
After a change or request
No, update only: The status is updated but not sent.
On change: The status is sent when a change occurs.
After request: The status is sent when a request occurs.
After a change or request: The status is sent on a change or a request.
E...H, p. 123.
fan, p. 258