ABB i-bus KNX Product Manual page 97

Fan coil actuators fca/s
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
Operation mode output C and D
Options:
This parameter determines whether the operation modes of outputs C and D can be parameterized
individually or whether the outputs are operated in operation mode Valve drive, motor-driven (3-point).
The outputs are linked to one another in pairs in this operation mode. Outputs C and D control the
contacts Open/Close of the valve drive for opening/closing the valve.
Individual: With this setting, the operation modes of outputs C and D are set individually from one
another.
Valve drive, motor-driven (3-point): The parameter (window) and communication objects for the
operation mode Valve drive, motor-driven (3-point) are enabled.
Assignment of the valves
Note
Outputs A and C are automatically assigned via the selection in the parameter Fan Coil operating mode.
Individual
Valve drive, motor-driven (3-point)
Dependent parameters:
Output C
Output D
Options:
Disabled
Valve drive, thermoelectric (PWM)
This parameter defines the individual operation mode of the output.
Disabled: No operation mode selected.
Valve drive, thermoelectric (PWM): The parameter (window) and communication objects for the
operation mode Valve drive, thermoelectric (PWM) are enabled.
Output C
Open
Output D
Close
FCA/S 1.x.x.1 | 2CDC508134D0202 95