ABB i-bus KNX Product Manual page 162

Fan coil actuators fca/s
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
Enable limitations
Options:
Selection of option Yes:
This function defines fan speed ranges (limitations) which may not be over/undershot.
160 2CDC508134D0202 | FCA/S 1.x.x.1
No
Yes
Dependent parameter:
Limitation 1
Limitation 2
Limitation 3
Limitation 4
Options:
3, 2, 1, OFF
Unchanged
OFF
1
1, OFF
2
2, 1
2, 1, OFF
3
3, 2
3, 2, 1
This parameter sets which fan speed is set, or may not be over/undershot, when forced operation is
active.
3, 2, 1, OFF: All states are possible.
Unchanged: The state is retained.
OFF: Off
1: Limited to speed 1.*
1, OFF: limited to speed 1 and off.
2: Limited to speed 2.*
2, 1: limited to speeds 2 and 1.
2, 1, OFF: limited to speed 2, 1 and off.
3: Limited to speed 3.*
3, 2: limited to speeds 3 and 2.
3, 2, 1: limited to speeds 3, 2 and 1.
* The control value is ignored.