ABB i-bus KNX Product Manual page 229

Fan coil actuators fca/s
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
No.
69
This communication object is enabled if automatic operation has been enabled in
level), p. 149.
Using this communication object the control value for automatic operation is predefined as a 1 byte value [0...255].
70
This communication object is enabled if automatic operation has been enabled in
level), p. 149, and two inputs have been activated by the parameter Number of control value inputs in
Automatic control
Using this communication object the second control value for automatic operation is predefined as a 1 byte value [0...255].
71
This communication object is enabled if two communication objects have been activated for the control values (control value
A and control value B) in
communication object.
72
This communication object is enabled if the parameter Activate monitoring control values has been selected with the option
Yes in
This communication object displays control value faults.
The blower actuator uses the Fault control value communication object to report a fault and then reacts according to the
parameterization for faults.
Telegram value:
73...79
Not assigned
Functionality
Control value A
(if 2 control values) or
Control value
(if only 1 control value)
Control value B
(if 2 control values)
(One-level), p. 156.
Toggle control value A/B
(if 2 control values)
Parameter window Automatic control
Fault control value
Parameter window Automatic control
0 = No fault
1 = Fault
Note
If no value is sent to the communication object Control value A, Control value B or Control Value for a set time, a
sender fault is assumed. If the communication object Toggle control value A/B receives a value, the monitoring time
is started.
communication object name
Fan E, F, G
Fan E, F, G
Fan E, F, G
(One-level), p. 156, and they are to be selected by a
Fan E, F, G
(One-level), p. 156.
Data type
Flags
1 byte
C, W
DPT 5.010
Parameter window E, F, G: Fan (One-
1 byte
C, W
DPT 5.010
Parameter window E, F, G: Fan (One-
Parameter window
1 bit
C, W
DPT 1.001
1 bit
C, R, T
DPT 1.005
FCA/S 1.x.x.1 | 2CDC508134D0202 227