Commissioning
3.3.3

Communication objects Valve drive, thermoelectric (PWM) and motor-driven (3-point)

Note
As the functions for all outputs are identical, only the functions of output A and A/B will be described.
No.
10
This communication object is enabled if the operating mode Valve drive, thermoelectric (PWM) has been selected in
Parameter window Enable output
the option Bit in
Telegram value:
10
This communication object is enabled if the operating mode Valve drive, thermoelectric (PWM) has been selected in
Parameter window Enable output
the option Byte in
The communication object value [0...255] determines the variable mark-to-space ratio of the valve drive. With communication
object value 0 the output switches OFF (valve is closed with normally closed valve drive). With communication object value
255 the output switches ON permanently (valve is fully open with normally open valve drive).
Telegram value:
10
This communication object is enabled if the operating mode Valve drive, motor-driven (3-point) has been selected in
Parameter window Enable output
The communication object value [0...255] determines the control value of the valve drive.
If the communication object value is 0, the output switches OFF (voltage 0 V).
If the communication object value is 255, the output switches ON permanently (full voltage).
Telegram value:
10
See communication object 10 Control value, heating, continuous (3-point)
Functionality
Control value, heating, ON/OFF
A...D, p. 76, and the parameter Control value is received as has been parameterized with
Parameter window A: Output (Valve drive, thermoelectric
0 = OFF
1 = ON
Control value, heating,
continuous (PWM)
A...D, p. 76, and the parameter Control value is received as has been parameterized with
Parameter window A: Output (Valve drive, thermoelectric
0 = OFF (valve drive closed)
x = Intermediate values
255 = ON (valve drive opened)
Control value, heating,
continuous (3-point)
A...D, p. 76.
0 = OFF (valve drive closed)
x = Intermediate values
255 = ON (valve drive opened)
Control value, heating,
analog (0...10 V)
communication object name
Output A
(PWM)), p. 97.
Output A
(PWM)), p. 97.
Output A/B
Output A
Data type
Flags
1 bit
C, W
DPT 1.001
1 byte
C, W
DPT 5.001
1 byte
C, W
DPT 5.001
1 byte
C, W
DPT 5.001
FCA/S 1.x.x.1 | 2CDC508134D0202 211