ABB i-bus
KNX
Commissioning
Enable communication object
"Switch 1"
Options:
Yes: The communication object Switch 1 appears.
176 2CDC508134D0202 | FCA/S 1.x.x.1
No
Yes
Dependent parameters:
Reaction on event 0
Options:
No edge evaluation
ON
OFF
Toggle
Terminate cyclic transmission
Reaction on event 1
Options:
No edge evaluation
ON
OFF
Toggle
Terminate cyclic transmission
The reaction of the communication object is determined here. If the option Yes has been selected
with the parameter Distinction between long and short operation, the reaction occurs with a short or
long operation. With the option No, it occurs with each edge change.
Important
If the option Terminate cyclic transmission is set, it is important to note that this is only effective if
the option Yes has only been selected in the parameter Send cyclically.