Mounting And Installation - ABB i-bus KNX Product Manual

Fan coil actuators fca/s
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Device technology
2.5

Mounting and installation

The device is a modular installation device for quick installation in distribution boards on 35 mm mounting
rails to DIN EN 60 715.
The installation position can be selected as required.
The electrical connection is implemented using screw terminals. The connection to the bus is implemented
using the supplied bus connection terminal. The terminal assignment is located on the housing.
The device is ready for operation after connection to the bus voltage.
The device must be accessible for operation, testing, visual inspection, maintenance and repair in
compliance with DIN VDE 0100-520.
Commissioning requirement
In order to commission the device, a PC with ETS, as well as a connection to the ABB i-bus
KNX interface, is required.
The device is ready for operation after the bus voltage is applied. No additional auxiliary voltage is
required.
Important
The maximum permissible current of a KNX line must not be exceeded.
During planning and installation ensure that the KNX line is correctly dimensioned.
The device has a maximum current draw of 12 mA.
Mounting and commissioning may only be carried out by electrical specialists. The applicable standards,
directives, regulations and specifications for the country in question should be observed when planning
and setting up electrical installations and security systems for intrusion and fire detection.
Protect the device from damp, dirt and damage during transport, storage and operation.
Only operate the device within the specified technical data!
The device should only be operated in an enclosed housing (distribution board)!
The voltage supply to the device must be switched off before mounting.
To avoid dangerous touch voltages which originate through feedback from differing phase conductors,
all poles must be disconnected when extending or modifying the electrical connections.
Manual operation
The device incorporates manual operating features. Special device functions can be undertaken using the
operating keys on the foil keypad.
The foil keypad may not be operated with pointed or sharp-edged objects, e.g. screwdrivers or pens. This
may damage the keypad.
Danger
®
, e.g. via a
FCA/S 1.x.x.1 | 2CDC508134D0202 59

Advertisement

Table of Contents
loading