Fan coil actuators fca/s
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
No.
61
This communication object is enabled if the parameter Enable limitations has been selected with the option Yes in
window Automatic control
The limitation 1 is active if a telegram with the value 1 is received on the communication object Limitation 1. The Limitation 1
is deactivated if a telegram with the value 0 is received on the communication object Limitation 1.
When Limitation 1 is activated, the fan can only assume the fan speed or speed range which has been set in the parameter
window Limitation 1.
Telegram value:
62
See communication object 61
63
See communication object 61
64
See communication object 61
65
This communication object is enabled if the parameter Enable communication object "Forced operation" 1-bit has been
selected with the option Yes in
If a forced operation is activated, the device switches to forced operation regardless of the control value and its
parameterized Limitation 1...4.
Telegram value:
224 2CDC508134D0202 | FCA/S 1.x.x.1
Functionality
Limitation 1
(One-level), p. 156.
Note
Limitation 1 is only active in automatic operation.
0 = Limitation x inactive
1 = Limitation x active
Limitation 2
Limitation 3
Limitation 4
Forced operation
Parameter window E, F, G: Fan
0 = No forced operation
1 = Forced operation
communication object name
Fan E, F, G
Fan E, F, G
(One-level), p. 149.
Data type
Flags
1 bit
C, W
DPT 1.003
Parameter
1 bit
C, W
DPT 1.003