ABB i-bus KNX Product Manual page 211

Fan coil actuators fca/s
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
No.
5
If there is a fault on an output, e.g. due to a short-circuit or overload, the LED A and B will flash. The communication object
Fault (overload/short-circuit) simultaneously sends a telegram with the value 1.
In the event of a fault on output A and/or B, these two outputs are switched off.
After the fault has been fixed, the fault is reset via the communication object Reset malfunction and the communication
object hast the value 0.
If the fault still persists, the LED will flash again, and the communication object has the value 1.
The communication object is always visible.
Telegram value:
6
A fault is reset via this communication object, e.g. short-circuit/overload LED flashes on the device.
A reset is only successful if the fault has been repaired and is no longer present.
The LED turns off after it is successfully reset.
There is no reaction should the value 1 be received during correct operation.
If a group address has not been assigned to this communication object, the fault can be reset when the device is restarted.
The communication object is always visible.
Telegram value:
7
See communication object 5
8
See communication object 6
Functionality
Fault (overload/short-circuit)
Note
Signaling via LED occurs only for the devices FCA/S 1.1.2.2 and FCA/S 1.2.2.2.
0 = No fault on the output.
1 = Fault on the output.
Reset malfunction
Note
Signaling via LED occurs only for the devices FCA/S 1.1.2.2 and FCA/S 1.2.2.2.
0 = No function
1 = Reset malfunction
Fault (overload/short-circuit)
Reset malfunction
communication object name
Output A
Output A/B
Output A
Output A/B
Output C
Output C/D
Output C
Output C/D
FCA/S 1.x.x.1 | 2CDC508134D0202 209
Data type
Flags
1 bit
C, R, T
DPT 1.005
1 bit
C, W, T
DPT 1.015
1 bit
C, R, T
DPT 1.005
1 bit
C, W, T
DPT 1.015