ABB i-bus KNX Product Manual page 133

Fan coil actuators fca/s
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
Enable communication object
"Status Fan speed" 1-byte
Options:
This status byte defines the figure value of the fan speed.
This display can be differentiated from Required fan speed by selecting Current fan speed. Initially, the
switchover times, dwell times and start-up phase must be completed before the required fan speed is
reached.
Yes: The communication object Status Fan speed is enabled.
No
Yes
Dependent parameters:
Meaning 1 byte
Options:
Current fan speed
Required fan speed
This parameter defines which status – Current fan speed or Required fan speed – is displayed.
What is current fan speed?
The Current fan speed is the speed at which the fan is actually operating.
What is required fan speed?
The Required fan speed is the fan speed which has to be reached, e.g. when the transition
and dwell times have elapsed.
Note
The limitations are included in this observation, i.e. if a limitation allows only fan speed 2,
the fan is operating at fan speed 2, and, for example, a telegram to switch up is received,
the required fan speed remains at 2, as fan speed 3 cannot be reached due to the
limitation.
Send object value
Options:
No, update only
On change
After request
After a change or request
No, update only: The status is updated but not sent.
On change: The status is sent when a change occurs.
After request: The status is sent when a request occurs.
After a change or request: The status is sent on a change or a request.
FCA/S 1.x.x.1 | 2CDC508134D0202 131