Function description
Configuration parameters for IEEE
1344 and C37.118 protocol
Application
The IED supports the following IEEE synchrophasor standards:
IEEE 1344-1995 (Both measurements and data communication)
IEEE Std C37.118-2005 (Both measurements and data communication)
IEEE Std C37.118.1–2011 and C37.118.1a-2014 (Measurements)
IEEE Std C37.118.2-2011 (Data communication)
PMUCONF contains the PMU configuration parameters for both IEEE C37.118
and IEEE 1344 protocols. This means all the required settings and parameters in
order to establish and define a number of TCP and/or UDP connections with one or
more PDC clients (synchrophasor client). This includes port numbers, TCP/UDP IP
addresses, and specific settings for IEEE C37.118 as well as IEEE 1344 protocols.
Operation principle
The Figure
32
demonstrates the communication configuration diagram. As can be
seen, the IED can support communication with maximum 8 TCP clients and 6 UDP
client groups, simultaneously. Every client can communicate with only one
instance of the two available PMUREPORT function block instances at a time. It
means that one client cannot communicate with both PMUREPORT:1 and
PMUREPORT:2 at the same time. However, multiple clients can communicate
with the same instance of PMUREPORT function block at the same time. For TCP
clients, each client can decide to communicate with an existing instance of
PMUREPORT by knowing the corresponding PMU ID for that PMUREPORT
instance. Whereas, for UDP clients, the PMUREPORT instance for each UDP
channel is defined by the user in the PMU and the client has to know the PMU ID
corresponding to that instance in order to be able to communicate. More
Wide area measurement system
IEC 61850
IEC 60617
identification
identification
PMUCONF
-
Section 6
GUID-747C6AD7-E6A1-466E-92D1-68865681F92F v1
GUID-1E140EA0-D198-443A-B445-47CEFD2E6134 v1
ANSI/IEEE C37.2
device number
-
GUID-33694C62-A109-4D8F-9063-CEFA5D0E78BC v4
GUID-2608FBC4-9036-476A-942B-13452019BC11 v2
99

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents