ABB REC670 Applications Manual page 462

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

Section 16
Logic
456
PROTECTION 1
START
FW
REV
PROTECTION 2
STL1
FWL1
REVL1
STL2
FWL2
REVL2
STL3
FWL3
REVL3
PROTECTION 3
STN
FWN
REVN
IEC16000180 V2 EN-US
Figure 201:
Example of the connection of directional start logic
The Start Matrix (SMAGAPC) merges start and directional output signals from
different application functions and creates a common directional output signal
(STDIR) to be connected to the Trip function (SMPPTRC). Protection functions
connect their directional data via the STARTCOMB function to SMAGAPC and
then to the SMPPTRC, or directly to SMAGAPC and then to the SMPPTRC.
The trip function (SMPPTRC) splits up the directional data as general output data
for START, STL1, STL2, STL3, STN, FW and REV.
STARTCOMB
STDIR
BLOCK
START
FW
REV
STL1
FWL1
REVL1
STL2
FWL2
REVL2
STL3
FWL3
REVL3
STN
FWN
REVN
STARTCOMB
BLOCK
STDIR
START
FW
REV
STL1
FWL1
REVL1
STL2
FWL2
REVL2
STL3
FWL3
REVL3
STN
FWN
REVN
STARTCOMB
BLOCK
STDIR
START
FW
REV
STL1
FWL1
REVL1
STL2
FWL2
REVL2
STL3
FWL3
REVL3
STN
FWN
REVN
1MRK 511 401-UEN A
SMAGAPC
SMPPTRC
BLOCK
STDIR
BLOCK
STDIR1
BLKLKOUT
STDIR2
TRIN
STDIR3
TRINL1
STDIR4
TRINL2
STDIR5
TRINL3
STDIR6
PSL1
STDIR7
PSL2
STDIR8
PSL3
STDIR9
1PTRZ
STDIR10
1PTREF
STDIR11
P3PTR
STDIR12
SETLKOUT
STDIR13
RSTLKOUT
STDIR14
STDIR
STDIR15
STDIR16
PROTECTION 4
-
STDIR
-
-
Bay control REC670 2.2 IEC
Application manual
TRIP
TRL1
TRL2
TRL3
TR1P
TR2P
TR3P
CLLKOUT
START
STL1
STL2
STL3
STN
FW
REV
IEC16000180-2-en.vsdx