Section 23
Basic IED functions
23.4.2
23.5
23.5.1
23.5.2
23.5.3
23.6
23.6.1
580

Setting guidelines

The setting ActiveSetGrp, is used to select which parameter group to be active. The
active group can also be selected with configured input to the function block
SETGRPS.
The length of the pulse, sent out by the output signal SETCHGD when an active
group has changed, is set with the parameter t.
The parameter MAXSETGR defines the maximum number of setting groups in use
to switch between. Only the selected number of setting groups will be available in
the Parameter Setting tool (PST) for activation with the ActiveGroup function
block.
Rated system frequency PRIMVAL
Identification
Function description
Primary system values
Application
The rated system frequency and phase rotation direction are set under Main menu/
Configuration/ Power system/ Primary Values in the local HMI and PCM600
parameter setting tree.
Setting guidelines
Set the system rated frequency. Refer to section
SMAI"
for description on frequency tracking.
Summation block 3 phase 3PHSUM
Application
The analog summation block 3PHSUM function block is used in order to get the
sum of two sets of 3 phase analog signals (of the same type) for those IED
functions that might need it.
IEC 61850
IEC 60617
identification
identification
PRIMVAL
-
"Signal matrix for analog inputs
1MRK 511 401-UEN A
M15259-3 v4
IP15064-1 v2
GUID-B8B3535D-227B-4151-9E98-BEB85F4D54DE v1
ANSI/IEEE C37.2
device number
-
M15288-3 v6
M15292-3 v2
SEMOD55968-1 v2
SEMOD56004-4 v3
Bay control REC670 2.2 IEC
Application manual