ABB REC670 Applications Manual page 123

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

1MRK 511 401-UEN A
Bay control REC670 2.2 IEC
Application manual
IEC140000131 V1 EN-US
Figure 45:
3PHSUM setting parameters example-showing that 3PHSUM is
using the External DFT reference coming indirectly from SMAI3
Figure
46
shows an example of wrong connection of 3PHSUM and
PHASORREPORT blocks in ACT where SMAI3 is configured as the reference
block for DFT reference external out (DFTRefExtOut) and 3PHSUM uses external
DFT reference (from SMAI3).
IEC140000132 V2 EN-US
Figure 46:
An example of wrong connection of 3PHSUM and
PHASORREPORT blocks in ACT
If settings for PMUREPORT instances (PHASORREPORT1 instances 1 and 2
above) differ for SvcClass or ReportRate, then the synchrophasor reported by
PHASOR2 connection from PHASORREPORT1 instance 2 will not be compliant
with IEEE C37.118 standard. The reason is as in the rule 2, the filtering in SMAI/
3PHSUM block is adapted according to the performance class (SvcClass) and
reporting rate of the connected instance of PHASORREPORT function block. On
the other hand, when 3PHSUM uses external DFT reference, it also adapts its
filtering according to the SMAI reference block. Therefore, in order to avoid two
Wide area measurement system
Section 6
IEC140000131-1-en
IEC140000132-2-en.vsd
117