ABB REC670 Applications Manual page 111

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

1MRK 511 401-UEN A
Bay control REC670 2.2 IEC
Application manual
IEC140000119 V2 EN-US
Figure 34:
Multiple instances of PHASORREPORT blocks
Figure
35
shows both instances of ANALOGREPORT function blocks. The
instance number is visible in the bottom of each function block. For each instance,
there are three separate ANALOGREPORT blocks capable of reporting up to 24
Analog signals (8 Analog signals in each ANALOGREPORT block). These can
include for example transfer of active and reactive power or reporting the
milliampere input signals to the PDC clients as defined in IEEE C37.118 data
frame format.
IEC140000120 V2 EN-US
Figure 35:
Multiple instances of ANALOGREPORT blocks
Figure
36
shows both instances of BINARYREPORT function blocks. The instance
number is visible in the bottom of each function block. For each instance, there are
three separate BINARYREPORT blocks capable of reporting up to 24 Binary
signals (8 Binary signals in each BINARYREPORT block). These binary signals
can be for example dis-connector or breaker position indications or internal/
external protection alarm signals.
Wide area measurement system
IEC140000119-2-en.vsd
IEC140000120-2-en.vsd
Section 6
105