Armode = 1Ph + 1*2/3Ph, 1-Phase, 2-Phase Or 3-Phase Reclosing In The First Shot - ABB REC670 Applications Manual

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

1MRK 511 401-UEN A
14.2.2.13
14.2.2.14
Bay control REC670 2.2 IEC
Application manual
more shots are attempted. The expression "1*3ph" should be understood as "Only
one shot at three-phase auto reclosing".
ARMode = 1ph + 1*2/3ph, 1-phase, 2-phase or 3-phase reclosing in
the first shot
At single-phase or two-phase tripping, the operation is as in the above described
example, program mode 1/2/3ph. If the first reclosing shot fails, a three-phase trip
will be issued and three-phase reclosing will follow, if selected. At two-phase or
three-phase trip a failure of a two-phase or three-phase auto reclosing attempt will
inhibit the auto recloser. No more shots are attempted. The expression "1*2/3ph"
should be understood as "Only one shot at two-phase or three-phase auto
reclosing".
Table 32:
Type of reclosing shots at different settings of ARMode or integer inputs to
MODEINT
MODEINT (integer)
1
2
3
4
1ph + 1*2ph
5
1/2ph + 1*3ph
6
1ph + 1*2/3ph
A start of a new auto reclosing cycle during the set "reclaim time" is blocked when
the set number of reclosing shots have been reached.
External selection of auto reclosing mode
The auto reclosing mode can be selected by use of available logic function blocks.
Below is an example where the choice of mode, ARMode=3ph or
ARMode
Type of fault
1ph
3ph
2ph
3ph
1ph
1/2/3ph
2ph
3ph
1ph
1/2ph
2ph
3ph
1ph
2ph
3ph
1ph
2ph
3ph
1ph
2ph
3ph
Section 14
Control
M12391-146 v5
1st shot
2nd-5th shot
3ph
3ph
3ph
3ph
3ph
3ph
1ph
3ph
2ph
3ph
3ph
3ph
1ph
3ph
2ph
3ph
.....
.....
1ph
3ph
2ph
.....
.....
.....
1ph
3ph
2ph
3ph
3ph
.....
1ph
3ph
2ph
.....
3ph
.....
M12391-241 v5
309