Section 14
Control
386
Line voltage drop
The purpose with the line voltage drop compensation is to control the voltage, not
at the power transformer low voltage side, but at a point closer to the load point.
Figure
172
shows the vector diagram for a line modelled as a series impedance
with the voltage U
at the LV busbar and voltage U
B
current on the line is I
, the line resistance and reactance from the station busbar to
L
the load point are R
and X
L
current, is j. If all these parameters are known U
vector calculation.
Values for R
and X
are given as settings in primary system ohms. If more than
L
L
one line is connected to the LV busbar, an equivalent impedance should be
calculated and given as a parameter setting.
The line voltage drop compensation function can be turned On/Off by the setting
parameter OperationLDC. When it is enabled, the voltage U
Automatic voltage control for tap changer function, TR1ATCC for single control
and TR8ATCC for parallel control for voltage regulation instead of U
TR1ATCC or TR8ATCC will still perform the following two checks:
1.
The magnitude of the measured busbar voltage U
range, (setting Umin and Umax). If the busbar voltage falls-out of this range
the line voltage drop compensation calculations will be temporarily stopped
until the voltage U
B
2.
The magnitude of the calculated voltage U
such that it is only allowed to be equal to or smaller than the magnitude of U
otherwise U
will be used. However, a situation where U
B
by a capacitive load condition, and if the wish is to allow for a situation like
that, the limitation can be removed by setting the parameter OperCapaLDC to
On.
~
U
L
IEC06000487 V2 EN-US
Figure 172:
Vector diagram for line voltage drop compensation
. The angle between the busbar voltage and the
L
comes back within the range.
L
R
X
L
L
U
B
U
B
jX
I
L
L
Re
R
I
L
L
IEC06000487-2-en.vsd
1MRK 511 401-UEN A
at the load center. The load
L
can be obtained by simple
L
will be used by the
L
. However,
B
, shall be within the security
B
at the load point, can be limited
>U
can be caused
L
B
Bay control REC670 2.2 IEC
Application manual
SEMOD159053-105 v6
,
B