Setting Guidelines - ABB REC670 Applications Manual

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

1MRK 511 401-UEN A
17.7.3
17.8
17.8.1
17.8.2
Bay control REC670 2.2 IEC
Application manual
When an input is set, the respective output is set for a user defined time. If the
input signal remains set for a longer period, the output will remain set until the
input signal resets.
INPUTn
OUTPUTn
IEC09000732 V1 EN-US
Figure 212:
BINSTATREP logical diagram

Setting guidelines

The pulse time t is the only setting for the Logical signal status report
(BINSTATREP). Each output can be set or reset individually, but the pulse time
will be the same for all outputs in the entire BINSTATREP function.
Fault locator LMBRFLO
Identification
Function description
Fault locator
Application
The main objective of line protection and monitoring IEDs is fast, selective and
reliable operation for faults on a protected line section. Besides this, information on
distance to fault is very important for those involved in operation and maintenance.
Reliable information on the fault location greatly decreases the downtime of the
protected lines and increases the total availability of a power system.
The fault locator is started with the input CALCDIST to which trip signals
indicating in-line faults are connected, typically distance protection zone 1 and
accelerating zone or the line differential protection. The disturbance report must
also be started for the same faults since the function uses pre- and post-fault
information from the trip value recorder function (TVR).
Beside this information the function must be informed about faulted phases for
correct loop selection (phase selective outputs from differential protection, distance
t
IEC09000732-1-en.vsd
IEC 61850
IEC 60617
identification
identification
LMBRFLO
-
Section 17
Monitoring
t
GUID-BBDA6900-4C1A-4A7C-AEA5-3C49C2749254 v2
IP14592-1 v2
M14892-1 v3
ANSI/IEEE C37.2
device number
-
M13752-3 v6
501

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents