Section 14
Control
14.9.2
14.9.3
14.10
14.10.1
428

Application

The Single point generic control 8 signals (SPC8GAPC) function block is a
collection of 8 single point commands that can be used for direct commands for
example reset of LED's or putting IED in "ChangeLock" state from remote. In this
way, simple commands can be sent directly to the IED outputs, without
confirmation. Confirmation (status) of the result of the commands is supposed to
be achieved by other means, such as binary inputs and SPGAPC function blocks.
PSTO is the universal operator place selector for all control
functions. Even if PSTO can be configured to allow LOCAL or
ALL operator positions, the only functional position usable with the
SPC8GAPC function block is REMOTE.
Setting guidelines
The parameters for the single point generic control 8 signals (SPC8GAPC)
function are set via the local HMI or PCM600.
Operation: turning the function operation On/Off.
There are two settings for every command output (totally 8):
PulseModex: decides if the command signal for output x is Latched (steady) or
Pulsed.
tPulsex: if PulseModex is set to Pulsed, then tPulsex will set the length of the pulse
(in seconds).
AutomationBits, command function for DNP3.0
AUTOBITS
Identification
Function description
AutomationBits, command function for
DNP3
IEC 61850
IEC 60617
identification
identification
AUTOBITS
-
1MRK 511 401-UEN A
SEMOD176511-4 v6
SEMOD176518-4 v6
SEMOD158589-1 v3
GUID-C3BB63F5-F0E7-4B00-AF0F-917ECF87B016 v4
ANSI/IEEE C37.2
device number
-
Bay control REC670 2.2 IEC
Application manual