The setting of DU> should be set high (approximately 60% of UBase) and the
current threshold DI< low (approximately 10% of IBase) to avoid unwanted
operation due to normal switching conditions in the network. The delta current and
delta voltage function shall always be used together with either the negative or zero
sequence algorithm. If USet
ISet
the primary current for operation of dI/dt, the setting of DU> and DI< will
prim
be given according to equation
USet
prim
.
> =
DU
100
UBase
EQUATION1523 V3 EN-US
ISet
prim
.
< =
DI
100
IBase
EQUATION1524 V4 EN-US
The voltage thresholds UPh> is used to identify low voltage condition in the
system. Set UPh> below the minimum operating voltage that might occur during
emergency conditions. A setting of approximately 70% of UBase is recommended.
The current threshold IPh> shall be set lower than the IMinOp for the distance
protection function. A 5...10% lower value is recommended.

Dead line detection

The condition for operation of the dead line detection is set by the parameters
IDLD< for the current threshold and UDLD< for the voltage threshold.
Set the IDLD< with a sufficient margin below the minimum expected load current.
A safety margin of at least 15-20% is recommended. The operate value must
however exceed the maximum charging current of an overhead line, when only one
phase is disconnected (mutual coupling to the other phases).
Set the UDLD< with a sufficient margin below the minimum expected operating
voltage. A safety margin of at least 15% is recommended.
Fuse failure supervision VDSPVC
Identification
Function description
Fuse failure supervision
is the primary voltage for operation of dU/dt and
prim
112
and equation 113.
IEC 61850
identification
VDSPVC
1MRK 511 401-UEN A
(Equation 112)
(Equation 113)
GUID-9C5BA1A7-DF2F-49D4-A13A-C6B483DDFCDC v2
GUID-109434B0-23E5-4053-9E6E-418530A07F9C v2
IEC 60617
ANSI/IEEE C37.2
identification
device number
VTS
60
Bay control REC670 2.2 IEC
Application manual
M13683-78 v4