1MRK 511 401-UEN A
14.7
14.7.1
14.7.2
Bay control REC670 2.2 IEC
Application manual
OutType: Steady or Pulsed.
tPulse: In case of a pulsed output, it gives the length of the pulse (in seconds).
tDelay: The delay between the UP or DOWN activation signal positive front and
the output activation.
StopAtExtremes: Sets the behavior of the switch at the end positions – if set to
Disabled, when pressing UP while on first position, the switch will jump to the last
position; when pressing DOWN at the last position, the switch will jump to the first
position; when set to Enabled, no jump will be allowed.

Selector mini switch VSGAPC

Identification
Function description
Selector mini switch
Application
Selector mini switch (VSGAPC) function is a multipurpose function used in the
configuration tool in PCM600 for a variety of applications, as a general purpose
switch. VSGAPC can be used for both acquiring an external switch position
(through the IPOS1 and the IPOS2 inputs) and represent it through the single line
diagram symbols (or use it in the configuration through the outputs POS1 and
POS2) as well as, a command function (controlled by the PSTO input), giving
switching commands through the CMDPOS12 and CMDPOS21 outputs.
The output POSITION is an integer output, showing the actual position as an
integer number 0 – 3, where 0 = MidPos, 1 = Open, 2 = Closed and 3 = Error.
An example where VSGAPC is configured to switch Autorecloser on–off from a
button symbol on the local HMI is shown in figure185. The I and O buttons on the
local HMI are normally used for on–off operations of the circuit breaker.
IEC 61850
IEC 60617
identification
identification
VSGAPC
-
Section 14
Control
SEMOD158754-1 v3
SEMOD167850-2 v4
ANSI/IEEE C37.2
device number
43
SEMOD158803-5 v8
425