However, in some cases, the following rated secondary currents are used as well:
•
2A
•
10A
The IED fully supports all of these rated secondary values.
It is recommended to:
•
use 1A rated CT input into the IED in order to connect CTs
with 1A and 2A secondary rating
•
use 5A rated CT input into the IED in order to connect CTs
with 5A and 10A secondary rating
Example on how to connect a star connected three-phase CT set to
the IED
Figure
13
gives an example about the wiring of a star connected two-phase CT set
to the IED. It gives an overview of the actions which are needed to make this
measurement available to the built-in protection and control functions within the
IED as well.
For correct terminal designations, see the connection diagrams