When internal voltage selection is needed, the voltage transformer circuit
connections are made according to figure 110. The voltage from the busbar 1 VT is
connected to U3PBB1 and the voltage from busbar 2 is connected to U3PBB2. The
voltage from the line VT is connected to U3PLN1. The positions of the
disconnectors and VT fuses shall be connected as shown in figure 110. The voltage
selection parameter CBConfig is set to Double bus.

Double circuit breaker

WA1
WA2
WA2_
WA1_MCB
MCB
WA1_QA1
WA2_QA1
LINE_MCB
LINE
IEC10000096 V4 EN-US
Figure 111:
Connections of the SESRSYN function block in a double breaker
arrangement
A double breaker arrangement requires two function blocks, one for breaker
WA1_QA1 and one for breaker WA2_QA1. No voltage selection is necessary,
because the voltage from busbar 1 VT is connected to U3PBB1 on SESRSYN for
WA1_QA1 and the voltage from busbar 2 VT is connected to U3PBB1 on
SESRSYN for WA2_QA1. The voltage from the line VT is connected to U3PLN1
on both function blocks. The condition of VT fuses shall also be connected as
shown in figure 110. The voltage selection parameter CBConfig is set to No voltage
sel. for both function blocks.
1 1/2 circuit breaker
Figure
112
describes a 1 ½ breaker arrangement with three SESRSYN functions in
the same IED, each of them handling voltage selection for WA1_QA1, TIE_QA1
and WA2_QA1 breakers respectively. The voltage from busbar 1 VT is connected
to U3PBB1 on all three function blocks and the voltage from busbar 2 VT is
connected to U3PBB2 on all three function blocks. The voltage from line1 VT is
connected to U3PLN1 on all three function blocks and the voltage from line2 VT is
WA1_VT
GRP_OFF
LINE_VT
WA1_MCB
WA2_MCB
WA1_MCB
LINE_MCB
WA1_VT
WA2_VT
WA2_VT
GRP_OFF
LINE_VT
LINE_MCB
WA2_MCB
LINE_VT
LINE_MCB
Bay control REC670 2.2 IEC
1MRK 511 401-UEN A
M12329-3 v7
WA1_QA1
SESRSYN
U3PBB1*
U3PBB2*
U3PLN1*
U3PLN2*
UB1OK
UB1FF
ULN1OK
ULN1FF
WA2_QA1
SESRSYN
U3PBB1*
U3PBB2*
U3PLN1*
U3PLN2*
UB1OK
UB1FF
ULN1OK
ULN1FF
IEC10000096-6-en.vsd
M12330-3 v8
Application manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents