ABB REC670 Applications Manual page 557

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

1MRK 511 401-UEN A
Bay control REC670 2.2 IEC
Application manual
SYNCH signal on the MUx function block indicates that protection functions
are blocked due to loss of internal time synchronization to the IED (that is loss
of the hardware synchSrc).
MUSYNCH signal on the MUx function block monitors the synchronization
flag smpSynch in the datastream and IED hardware time synchronization.
No time synchronization
This example is not valid when GPS time is used for differential
protection, when PTP is enabled or when the PMU report is used.
IED
IEC/UCA 61850-9-2LE
Data
MU
IEC10000075=2=en=Original.vsd
IEC10000075 V2 EN-US
Figure 233:
Setting example without time synchronization
It is also possible to use IEC/UCA 61850-9-2LE communication without time
synchronization.
Settings on the local HMI under Main menu/Configuration/Time/
Synchronization/TIMESYNCHGEN:1/IEC61850-9-2:
HwSyncSrc: set to Off
SyncLostMode: set to No block to indicate that protection functions are not
blocked
SyncAccLevel: set to unspecified
Two status monitoring signals with no time synchronization:
Section 20
Station communication
551