ABB REC670 Applications Manual page 125

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

1MRK 511 401-UEN A
Bay control REC670 2.2 IEC
Application manual
Each category has its corresponding parameter settings except for
BINARYREPORT function block which does not have any specific parameters and
settings.
1.
PMUREPORT is the main function block which controls the operation of other
PMU reporting function blocks. Each instance of PMUREPORT function
block has the following parameters:
Operation: Enables/Disables the operation of the corresponding instance
of PMU reporting functionality by choosing On/Off setting.
SvcClass: It refers to the 1-byte SVC_CLASS field of the configuration
frame 3 (CFG-3) organization defined in IEEE C37.118.2 message
format. Here the user can select the performance class (service class)
used for synchrophasor data measurement according to IEEE C37.118.1
standard. The options are P class or M class.
Note: There are 2 PMUREPORT instances available (PMUREPORT:1
and PMUREPORT:2) corresponding to 2 independent data streams. The
user can set different or identical service class for each data stream. In
case of different service classes, special rules shall be considered in
PCM600 ACT for the connection of preprocessor blocks (SMAI) and
3PHSUM blocks to PHASORREPORT blocks. More details are
available under section
in PCM600 Application Configuration Tool
Global_PMU_ID: It refers to the 16-byte G_PMU_ID field of the
configuration frame 3 (CFG-3) organization defined in IEEE C37.118.2
message format. It is a 16-character (128 bits) user-assigned value which
can be sent with the configuration 3 message. It allows uniquely
identifying PMUs in a system that has more than 65535 PMUs. The
coding for the 16 bytes is left to the user for assignment.
PMUdataStreamIDCODE: It refers to the 2-byte IDCODE field of the
configuration frame and data frame organization defined in IEEE
C37.118.2 message format. It is a user assigned ID number (1-65534) for
each data stream sent out from the PMU. This is especially important
when having multiple data streams (multiple PMU functionality).
Note: The data stream IDCODE is a unique code for each and every data
stream in one physical PMU device. In the IED, there are 2
PMUREPORT instances available (PMUREPORT:1 and PMUREPORT:
2) corresponding to 2 independent data streams. The user must set
different IDCODEs for each instance.
PhasorFormat: It refers to the Bit 0 of the FORMAT field of the
configuration frames 1, 2 and 3 organization defined in IEEE C37.118.2
message format. Here the user can select the format of the calculated
synchrophasors. The options are Rectangular or Polar format.
Rectangular format represents the synchrophasor as real and imaginary
values, real value first (a + bj) while the Polar format represents the
synchrophasor as magnitude and angle, magnitude first (A e
PhasorDataType: It refers to the Bit 1 of the FORMAT field of the
configuration frames 1, 2 and 3 organization defined in IEEE C37.118.2
message format. Here the user can select the data type of the calculated
synchrophasors. The options are Integer or Float data. The
Wide area measurement system
PMU Report Function Blocks Connection Rules
(ACT).
Section 6
).
119