Error messages
4.3 Errors from the communications module/reader
Error mes-
Description
sage
(hex)
0xE2FE0100
Field disturbance on reader
Reader is receiving interference pulses from the environment.
External interference field. The interference field can be detected with the "inductive field indicator"
of the STG.
The distance between two readers is too short and does not correspond to the configuration guide-
lines
The connecting cable to the reader is disrupted, too long or does not comply with the specification
MOBY U: Transponder has left the antenna field during communication.
MOBY U: Communication between reader and transponder was aborted due to a disruption (e.g.
person/foreign body moving between reader and transponder).
Too many transmit errors
The transponder was unable to receive the command or the write data from the communications mod-
ule correctly even after several attempts.
The transponder is positioned exactly in the limit area of the transmission window
Data transmission to the transponder is being affected by external interference
CRC sending error
The transponder reports CRC error frequently (transponder is positioned in the limit area of the
reader; transponder and/or reader has a hardware defect)
Only during initialization: CRC error on receipt of acknowledgement from transponder (cause as for
field interference on the reader)
When formatting, the transponder must be in the transmission window of the reader, otherwise a
timeout error will occur, in other words:
The transponder is located exactly in the limit area of the transmission window
The transponder is consuming too much power (defective)
Bad "FORMAT" parameter setting for EEPROM transponder
RF600:
No ETSI channel free
Incorrect communication standard selected in the "INIT" command
Bad expert parameter
Power check of the ETSI wireless profile is incorrect
0xE2FE0200
More transponders are located in the transmission window than can be processed at the same time by
the reader.
There is more than one transponder in the transmission window.
RF620R/RF630R: Transponder power supply close to limit.
Increase the antenna power or reduce the distance to the transponder.
0xE2FE8100
There is no transponder with the required EPC-ID in the transmission window or there is no transponder at
all in the antenna field.
0xE2FE8200
The requested data is not available.
0xE2FE8300
The transponder signals a CRC error.
0xE2FE8400
The selected antenna is not enabled.
0xE2FE8500
The selected frequency is not enabled.
124
Ident profile and Ident blocks, standard function for Ident systems
Function Manual, 10/2018, C79000-G8976-C387-04