Setting parameters for blocks
3.4 Programming Ident blocks
3.4.3.4

Reset_RF200

Figure 3-26
Table 3- 31
Parameter
TAG_CONTROL
TAG_TYPE
RF_POWER
54
"Reset_RF200" block
Explanation of the "Reset_RF200" block
Data type
Byte
Byte
Byte
Default values
Description
1
Presence check
1
Transponder type:
1 = every ISO transponder
3 = MDS D3xx - optimization
4
Output power; only relevant for
RF290R
RF power from 0.5 W to 5 W in incre-
ments of 0.25 W (range of values:
0x02 ... 0x14).
Default value 0x04 ≙ 1 W.