Error messages
4.3 Errors from the communications module/reader
Error mes-
Description
sage
(hex)
0xE4FE8C00
Communication error between Ident profile and communications module. Handshake error.
UDT of this communications module is overwritten by other program sections
Check parameter settings of communications modules in the UDT
Check the Ident profile command that caused this error
Start "INIT" after correcting the error
Backplane bus / PROFIBUS DP
Backplane bus / PROFIBUS DP / PROFINET bus connection was interrupted (wire break on the
bus; bus connector on the communications module was briefly unplugged)
Backplane bus / PROFIBUS DP / PROFINET master no longer addressing communications mod-
ule
Execute "INIT"
The communications module has detected a frame interruption on the bus. The backplane bus,
PROFIBUS or PROFINET may have been reconfigured (e.g. with HW Config or TIA Portal)
This error is only indicated when "Watchdog" has been enabled in the PROFIBUS configuration.
1)
0xE4FE8D00
Internal communications error of the communications module/reader
Connector contact problem on the communications module / reader
Hardware of the communications module / reader has a defect; → Send in communications module
/ reader for repair
Start "INIT" after correcting the error
Internal monitoring error of the communications module/reader
Program execution error on the communications module / reader
Turn the power supply of the communications module/reader off and on again
Start "INIT" after correcting the error
MOBY U: Watchdog errror on the reader
0xE4FE8E00
Active command canceled by "WRITE-CONFIG" ("INIT" or "SRESET") or bus connector unplugged
Communication with the transponder was aborted by "INIT"
This error can only be reported if there is an "INIT" or "SRESET"
0xE5FE0100
Incorrect sequence number order (SN) on the reader/communications module
0xE5FE0200
Incorrect sequence number order (SN) in the Ident profile
Possible cause: User mode "Ident profile/RFID standard profile" is not set in the device configuration.
0xE5FE0400
Invalid data block number (DBN) on the reader/communications module
0xE5FE0500
Invalid data block number (DBN) in the Ident profile
0xE5FE0600
Invalid data block length (DBL) on the reader/communications module
0xE5FE0700
Invalid data block length (DBL) in the Ident profile
126