3.4.3

Reset blocks

The reset blocks described in this section are required when you want to operate the optical
reader systems MV400/MV500 or the communications modules RF18xC, RF180C, ASM 456
with a SIMATIC S7-1200/S7-1500 controller. As an alternative you can also use these blocks
for the RF120C if you have selected the appropriate setting in the device configuration.
In the system, these reset blocks have the same function as the "Reset_Reader" block
described earlier. However, with the blocks described here, you need to set reader-
dependent parameters.
Remember that the default value will be used automatically if you do not select a value
manually.
3.4.3.1

Reset_MOBY_D

Figure 3-23
Table 3- 28
Parameter
TAG_CONTROL
TAG_TYPE
RF_POWER
Ident profile and Ident blocks, standard function for Ident systems
Function Manual, 10/2018, C79000-G8976-C387-04
"Reset_MOBY_D" block
Explanation of the "Reset_MOBY_D" block
Data type
Bool
Byte
Byte
Default values
Description
True
Presence check
1
Transponder type:
1 = every ISO transponder
0
Output power
RF power from 0.5 W to 10 W in in-
crements of 0.25 W
(range of values: 0x02 ... 0x28)
Setting parameters for blocks
3.4 Programming Ident blocks
51