Siemens SINAMICS S120 Commissioning Manual page 113

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

What to do?
4.
Configuration of
the drives
4.1
Inserting drives
4.2
Configuring the
control structure
4.3
Configuring the
power unit
Caution
If a sine-wave filter is connected, then it must be activated here as otherwise it could be destroyed!
4.4
Configuration,
power unit BICO
interconnection
4.5
Configuring
additional data
Commissioning Manual
Commissioning Manual, (IH1), 01/2012, 6SL3097-4AF00-0BP2
2.6 First commissioning control mode vector U/f in booksize format
You must individually configure the drives in the offline mode.
The wizard displays the data determined automatically from the
electronic type plate.
1. Double-click in the project tree on "Drives".
2. Double-click on the entry "Insert drives".
The configuration wizard of the drives is opened.
1. Enter a name for the drive.
2. Click on "OK".
1. Select function modules.
2. Switch the closed-control to "U/f control".
3. Select the required control mode.
4. Click on "Continue >".
1. Enter a name for the component.
2. Select the DC supply voltage.
3. Select the cooling type.
4. Select the baud rate.
5. Select the required power unit.
6. Click on "Continue >".
If an infeed without DRIVE-CLiQ connection is used, a message
is displayed stating that the operating signal must be connected.
1. In the following dialog "Infeed operational", set parameter
p0864 = 1.
2. Click on "Continue >".
In this window, you can additionally select the following
Various output filters
A Voltage Sensing Module
A parallel connection
How to do it?
Commissioning
Comment
-
-
-
-
-
With this dialog window,
the configuration of the
Motor Module has been
completed.