Siemens SINAMICS S120 Commissioning Manual page 187

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Control Unit 320-2 DP in operation
Table 3- 4
Control Unit CU320-2 DP – Description of the LEDs after booting
LED
Color
RDY (READY)
-
Green
Red
Red/
green
Orange
Green /
orange
or
red /
orange
DP
PROFIdrive
cyclic
operation
Green
Commissioning Manual
Commissioning Manual, (IH1), 01/2012, 6SL3097-4AF00-0BP2
State
OFF
Electronic power supply is missing or outside
permissible tolerance range.
Continuous
The component is ready for operation and cyclic
light
DRIVE-CLiQ communication is taking place.
Flashing
Commissioning / reset
light
0.5 Hz
Flashing
Writing to the memory card
light
2 Hz
Flashing
General errors
light
2 Hz
Flashing
Control Unit is ready for operation.
light
However there are no software licenses.
0.5 Hz
Flashing
Updating the firmware of the DRIVE-CLiQ
light
components
0.5 Hz
Flashing
DRIVE-CLiQ component firmware update
light
complete. Wait for POWER ON for the
2 Hz
components in question.
Flashing
Component detection via LED is activated
light
(p0124[0]).
2 Hz
Note:
Both options depend on the LED state when
component detection is activated via
p0124[0] = 1.
Off
Cyclic communication has not (yet) taken place.
Note:
The PROFIdrive is ready to communicate when
the Control Unit is ready to operate (see LED
RDY).
Continuous
Cyclic communication is taking place.
light
Flashing
Full cyclic communication has not yet taken
light
place.
0.5 Hz
Possible causes:
The controller is not transferring any
setpoints.
During isochronous operation, no global
control (GC) or a faulty global control (GC) is
transferred by the controller.
Description, cause
Diagnostics
3.1 Diagnostics via LEDs
Remedy
Check power supply
Check
parameterization/configuratio
n data
Obtain licenses
Turn POWER ON for the
components in question