8. Click on the "View/Refresh (F5)" button to display the IP address and the NameOfStation
9. If the Ethernet interface is displayed as bus node, select the entry and click on the
10. Click on the button "Connect to selected target devices" and call the menu "Target
Note
The IP address and device name are stored on the memory card of the Control Unit in a
non-volatile fashion.
Parameterizing the interface using the expert list
● Assign the "Name of Station" using parameter p8900
● Assign the "IP Address of Station" using parameter p8901 (factory setting 169.254.11.22)
● Assign the "Default Gateway of Station" using parameter p8902 (factory setting 0.0.0.0)
● Assign the "Subnet Mask of Station" using parameter p8903 (factory setting 255.255.0.0)
● Activate the configuration with p8905 = 1
● Activate the configuration and save with p8905 = 2
Commissioning Manual
Commissioning Manual, (IH1), 01/2012, 6SL3097-4AF00-0BP2
= "The assigned name" in the entry for the bus node.
Note
If these two pieces of information are not be displayed in the entry for the bus node, close
the "Accessible nodes" dialog and search for nodes that can be accessed again.
"Accept" button.
The SINAMICS drive is displayed as new drive object in the project tree. You can now
configure the new drive unit.
system > Load > To target device", to load the project to the Control Unit memory card.
Commissioning
2.2 STARTER commissioning tool
67