What to do?
2.
Add individual drive
3
Configure the drive unit
Commissioning Manual
Commissioning Manual, (IH1), 01/2012, 6SL3097-4AF00-0BP2
How to do it?
1. Double-click in the project tree on "Insert single
drive unit".
The following settings are preassigned:
Device type: CU320-2 PN
Device version: 4.5 or higher
STARTER version: 4.3 or higher
Address type: PROFINET
Bus address: 169.254.11.22
2. If necessary, correct these settings.
Once you have created the project, you have to configure the drive unit. Some examples
are provided in the following Chapters.
Commissioning
2.4 Creating a project in STARTER
Comment
Information about the bus
address:
The PROFINET address of the
Control Unit must not be set for
initial commissioning.
When delivered, the TCP/IP
address of the Control Unit is set
to 169.254.11.22. The address
can be correspondingly changed
to meet individual requirements.