3.5 Fault and alarm messages
External triggering messages
If the appropriate binector input is interconnected with an input signal, fault 1, 2 or 3 or alarm
1, 2 or 3 can be triggered via an external input signal.
Once an external fault (1 to 3) has been triggered on the Control Unit drive object, this fault
is also present on all associated drive objects. If one of these external faults is triggered on a
different drive object, it is only present on that particular drive object.
BI: p2106
BI: p2107
BI: p2108
BI: p2112
BI: p2116
BI: p2117
Note
An external fault or alarm is triggered by a 1/0 signal.
An external fault and alarm do not usually mean that an internal drive message has been
generated. The cause of an external fault and warning should, therefore, be remedied
outside the drive.
3.5.4

Parameters and function diagrams for faults and alarms

Function diagrams (see SINAMICS S120/S150 List Manual)
● 1750 Overview diagram – monitoring functions, faults, alarms
● 8060 Diagnostics - Fault buffer
● 8065 Diagnostics - Alarm buffer
● 8070 Diagnostics - Fault/alarm trigger word (r2129)
● 8075 Diagnostics - Fault/alarm configuration
● 8134 Diagnostics - measuring sockets
244
––> External fault 1
––> External fault 2
––> External fault 3
––> External alarm 1
––> External alarm 2
––> External alarm 3
Commissioning Manual, (IH1), 01/2012, 6SL3097-4AF00-0BP2
––> F07860(A)
––> F07861(A)
––> F07862(A)
––> A07850(F)
––> A07851(F)
––> A07852(F)
Commissioning Manual