Position tracking
You can also activate position tracking for a 2-pole resolver. Please note, however, that the
resolver may not be moved more than half an encoder revolution (pole width) when switched
off. The activation and configuration of the position tracking is described in the chapter
"Position tracking".
EPOS - absolute encoder adjustment
If the 2-pole resolver is used as an absolute encoder for basic positioning (EPOS), the
absolute encoder adjustment must be performed:
● via STARTER (Basic positioner → Referencing) or
● via the expert list.
To do this, set reference point coordinate p2599 to the value corresponding to the
mechanical system and request the adjustment with p2507 = 2.
You will then need to back up the data from RAM to ROM.
2.16

Temperature sensors for SINAMICS components

The following table provides an overview of the SINAMICS drive system components
available with temperature sensor connections.
Safe electrical separation of the temperature sensors
Only temperature sensors that meet the electrical separation specifications laid out in
EN 61800-5-1 may be connected to terminals "+Temp" and "-Temp". If safe electrical
separation cannot be guaranteed (e.g. for linear motors or third-party motors), a Sensor
Module External SME120, SME125 or the Terminal Module TM120 must be used. If these
instructions are not complied with, there is a risk of electric shock!
Commissioning Manual
Commissioning Manual, (IH1), 01/2012, 6SL3097-4AF00-0BP2
DANGER
2.16 Temperature sensors for SINAMICS components